over speed protection device actuates, read and record
all instrument readings just prior to the point of
actuation and note on the data sheet that the protection
device actuated.
NOTE
This step is not applicable to generator
sets having governors that utilize a
threaded shaft and lock nut(s) or other
mechanical means as a method of
operator speed adjustment.
(h) Adjust the generator set frequency for
the minimum attainable frequency. Read and record
all instrument readings.
NOTE
This step is not applicable to generator
sets having governors that utilize a
threaded shaft and lock nut(s) or other
mechanical means as a method of
operator speed adjustment.
(i) Repeat 16-16c. (1) and 16-16c. (2)(a)
through (f) for each frequency.
d. Results. The data sheet shall show the maxi-
mum and minimum frequencies attained at rated load,
the maximum and minimum attainable frequencies at
no load and actuation of the protection devices (if
applicable). Compare these results with the require-
ments of Table 16-1.
16-17. Overspeed Protective Device Test.
a. General. To assure that adequate protection
is afforded the generator set against overspending,
the overspeed protective device must operate properly.
b. Apparatus. A frequency meter or tachometer
as described and illustrated in MIL-HDBK-705,
Methods 104.1 or 109.1 shall be required.
c. Procedure.
(1) Preparation for test. Connect the frequency
meter in accordance with the applicable figure of
MIL-HDBK-705, Method 205. l, Paragraph 205. 1.9,
or utilize the tachometer in accordance with the man-
ufacturers instructions. Electronic governor and
throttle stops must be deactivated.
(2) Test.
(a) Start and operate the generator set at
rated speed (frequency), rated voltage and no load.
(b) Slowly increase the engine speed until
the overspeed protective device actuates. Record
the speed of the generator set at this point, and the
malfunction indicator light indication.
CAUTION
Do not operate the set in excess of 125
percent of rated speed or as otherwise
limited in the procurement document.
(c) Attempt to start the set. Record if
starting is achieved.
If the set did not start, reset
the overspeed protective device.
(d) Repeat steps (a) through (c) above two
additional times.
d. Compare the test results with requirement of
Table 16-1.
16-18. Circuit Interrupter Test (Short Circuit).
a. General. A circuit interrupter is connected
between the generator voltage reconnection system
and the generator set output terminals to disconnect
the generator output from the load and also to protect
the generator from a short circuit. The circuit inter-
rupter is operated from a current sensor external
to the interrupter.
b. Apparatus. Instrumentation for measuring
load conditions shall be as described and illustrated
in MIL-HDBK-705. In addition, a non-inductive
shunt, as short-circuiting switch, galvanometers
mat thing net works, an oscillograph as described and
illustrated in MIL-HDBK-705, Method 106.1, para-
graph 106. 1.3 and galvanometers having a flat
frequency response (flat within plus or minus five
percent) from DC to 3,000 hertz will be required.
c. Procedure.
(1) Preparation for test.
(a) Connect the load and instrumentation in
accordance with the applicable figure of MIL-HDBK-
705, Method 205. 1, paragraph 205. 1. 10 for one
voltage and frequency.
(b) Connect the shunt, galvanometers
matching net work, oscillograph, and short-circuiting
switch as illustrated in figure 512. 1.I.
(2) Test.
(a) Start and operate the generator set at
rated voltage, rated frequency and rated load.
(b) Set the oscillograph time marker to a
minimum of 0. 01 seconds or use a 60 hertz timing
trace set the chart speed such that the individual
peaks of the current waveform are clearly visible
and adjust the peak -to-peak rated current amplitude
to a minimum of 0.5 inch (or approximately 12
millimeters).
16-9