(c) Prior to closing the short-circuiting
switch, record a portion of the steady state load for
calibration. With the same load conditions record
all instrument readings.
(d) With oscillograph still recording the
steady state current, close the short-circuiting
switch.
CAUTION
If the circuit interrupter fails to operate
within the specified time, remove the
short circuit to prevent damage. Note
the failure to operate on the data sheet.
(e) The generator set contains a short-
circuit malfunction indicator, check and record its
indication,
(f) Repeat steps (a) thru (e) above for each
possible short circuit condition
(g) Repeat steps (a) thru (f) above for both
voltage confections if applicable.
d. Results.
(1) From the oscillograms taken in 16-18c
(2)(d), determine the time between the indicated
closure of the short-circuiting switch and the opening
of the circuit interrupter. See figure 512.1-110
(2) Calculate the short-circuit current using
the peak-to-peak amplitudes of the current trace and
the steady state ammeter reading prior to applica-
tion of the short circuit.
See figure 512. l-II.
(3) Tabulate the above results and the mal-
function indicator indication for each line connection
at each voltage connection and compare the results
with the requirement in table 16-1.
16-19. Circuit Interrupter Test (overload Current)
a. General. A circuit interrupter is connected
bettween the generator voltage reconnection system
and the generator output terminals to disconnect the
generator output from the load and to protect the
generator from a sustained overload current. The
circuit interrupter is operated from a current sensor
external to the interrupter.
b. Apparatus.
Instrumentation for measuring
load condition field voltage and current shall
be as described and illustrated in MIL-HDBK-705.
In addition a stopwatch or an oscillograph with gal-
vanometer matching network and a non-inductive
shunt as described and illustrated in MIL-HDBK-705,
Method 106.1, paragraph 106. 1.3 and galvanometers
having a flat frequency respond (within plus or minus
5% from dc to 3000 Hz.
c. Procedure.
(1) Preparation for test. Connect the load and
field instrumentation in accordance with the appli-
cable figure of MIL-HDBK-705, Method 205.1, para-
graph 205.1.10 for one voltage and frequency,
CAUTION
If the circuit interrupter fails to operate
within the time specified in table 16-1
at any time during the performance of
this method, manually open the circuit
interrupter and reduce the load impen-
ance to rated value before reclosing
the circuit interrupter. Record on the
data sheet the failure of the interrupter
to operate and the total elapsed time
the overload was on the set.
(a) Start and operate the generator set at rated
voltage; rated frequency and rated load.
(b) Allow the generator set to stabilize at rated
load, voltage and frequency, During this period,
readings of the load and field instrumentation shall
be recorded at minimum intervals of 10 minutes.
If necessary, adjustments to the load, voltage and
frequency may be made to maintain rated load at
rated voltage and frequency. Adjustment to the load,
voltage or frequency shall be noted on the data sheet.
Stabilization will be considered to have occured when
four consecutive voltage and current readings of the
exciter field either remain unchanged or have only
minor variations about an equilibrium condition with
no evident continued increase or decrease in value
after the last load, voltage or frequency adjustment
has been made.
(c) In one step, increase the load current to
the overload current value specified in table 16-1
(the increase in current may be accomplished by
any practical means, e. g. reactively or using re-
duced voltage levels).
NOTE
The frequency shall be maintained at rated
conditions, the load current shall be kept
constant and the load current shall be bal-
anced equally among the phases. Simul-
taneously with the load current increase,
start the stopwatch.
(d) Record all load instrumentation and the
time, m seconds, required for the circuit interrup-
ter to operate.
(e) The generator set contains an overload
malfunction indicator, check and record its indi-
cation,
(f) Allow the generator set to cool at rated load
for a minimum of 15 minutes.
16-10