(2) Test.
(a) Start and operate the generator set and
allow the set to stabilize at rated load, rated voltage
and rated frequency.
During this period operate the
recording meter(s) at a chart speed of not less than
6 inches per hour, and record all instrument readings
including thermal instrumentation at minimum inter-
vals of 10 minutes. If necessary, adjustments to the
load, voltage and frequency may be made to maintain
rated load at rated voltage and frequency. Adjust-
ments to the voltage and frequency shall be limited to
those adjustments available to the operator, specifi-
tally adjustments to the voltage or frequency adjust
devices. On sets utilizing a droop-type speed control
system as the prime speed control, the speed and
droop portions of the control may be adjusted. No
other adjustments to the voltage and frequency control
systems shall be made.
Adjustments to load, voltage
or frequency controls shall be recorded on both the
data sheet and the recording chart(s) at the time of a
adjustment.
Stabilization shall be considered to have
occurred when four consecutive voltage and current
recorded readings of the generator (or exciter) field
either remain unchanged or have only minor varia-
tions about an equilibrium condition with no evident
continued increase or decrease in value after the last
adjustment to the load, voltage or frequency has been
made.
(b) After stabilization has occurred, drop
the load to no load and reapply rated load a number
of times (three should be sufficient) to assure that the
no load and rated load voltage and frequency values
are repeatable and that the frequency and voltage
regulation is within the limits specified in the pro-
curement document. If any adjustments are neces-
sary, paragraph (a) above must be repeated. Reapply
rated load.
(c) The recording meter chart speed(s)
shall be 12 inches per minute throughout the remain-
der of this test. At each of the following load condi-
tions (one step) operate the set for a minimum of 40
seconds (or the short-term stability period plus the
allowable recovery time as specified in the procure-
ment document).
During each load condition read and
record all instrument readings except thermal instru-
mentation (for three-phase sets it is not necessary to
record line-to-line voltages). Each load condition
shall be applied to the generator set in one step at the
end of the short -term stability period for the previous
load condition.
1.
2.
3.
The load conditions are:
Rated load
No load
Rated load
No load
Rated load
No load
Rated load
No load
3/4 rated load
No load
3/4 rated load
12. No load
13. 3/4 rated load
14. No load
15. 1/2 rated load
16. No load
17. 1/2 rated load
18. No load
19. 1/2 rated load
20. No load
21. 1/4 rated load
22. No load
23. 1/4 rated load
24. No load
25. 1/4 rated load
26. No load
27. Rated load
28. No load
29. Rated load
30. No load
31. Rated load
32. No load
(d) Repeat (a) through (c) for all voltage
connections) and frequency(ies).
d. Results.
(1) Prepare a chart giving for each load change
the momentary overshoot or undershoot and the re-
covery time.
For each constant load, give the max-
imum voltage variation,
(2) Referring to figure 16-1, begin by deter-
mining the observed (B) and steady -state (D) voltage
bandwidths.
(a) Mark numerically the stabilizations
occurring after each load change, starting with the
stabilization obtained before the first load change.
(b) Determine the observed voltage band-
width (B) by marking the maximum trace excursion
and minimum trace excursion in the stabilized
portion. Draw two lines parallel to the axis of chart
movement, one each passing through these maximum
and minimum trace excursions respectively.
(c) Draw a line (C) parallel to and equi-
distant from the edges of the observed voltage band-
width. Determined in (b) above,
(d) Using the rated voltage of the generator
and given requirements of table 16-1, calculate the
steady -state voltage bandwidth (D). Draw this
steady -state voltage bandwidth as two parallel lines,
parallel to and equidistant from the median (C) at
the observed voltage bandwidth.
(3) To determine the maximum voltage varia-
tion at constant load
(a) One-half the observed voltage bandwidth
(B) is the plus or minus value of voltage deviation
at constant load.
(b) Divide each of the values obtained in (a)
16-6