(b) Connect the frequency meter to one ofthe armature coils of the generator.(c) Provide separate excitation for theexciter field.(2) Test.(a) Start and operate the generator at ratedfrequency and at no load.(b) Adjust the excitation so that any one ofthe coil voltages is at rated value.(c) Read and record the generator frequency(speed) and the voltage of each armature coil.(2) Test.d. Generator with separate excitation(1) Determine from the data obtained in 16-13d.(2) the maximum and minimum armature coil voltages.(2) The voltage unbalance is the difference be-tween the maximum and minimum armature coilvoltages. To express this in percent divide thisdifference by rated armature coil voltage and multiplyby 100.(a) Start and operate the generator set andallow the set to stabilize at rated load, rated voltageand rated frequency.During this period record allinstrument readings including thermal instrumenta-tion at minimum intervals of 10 minutes. If necess-ary, adjustments to the load, voltage and frequencymay be made to maintain rated load at rated voltageand frequency.Adjustments to the voltage and fre-quency shall be limited to those adjustments avail-able to the operator, specifically adjustments to thevoltage or frequency adjust devices. On sets utili-zing a droop-type speed control system as the primespeed control, the speed and droop portions of thecontrol may be adjusted.No other adjustments to thevoltage and frequency control systems shall be made.Adjustments to load, voltage or frequency controlsshall be recorded on the data sheet at the time ofadjustment.Stabilization shall be considered to haveoccurred when four consecutive voltage and currentreadings of the generator (or exciter) field eitherremain unchanged or have only minor variationsabout an equilibrium condition with no evident contin-ued increase or decrease in value after the last ad-justment to the load, voltage, or frequency has beenmade.Voltage Unbalance (Coil), in percent =(3) Compare the results of step (2) above withthe requirements.16-14. Regulator Range Test.a. General.The voltage adjust device associatedwith the voltage regulator provided with the generatorset must have adjustment capable of varying the reg-ulated voltage throughout the limits and under thevarious load conditions and temperature ranges with-out causing the voltage droop of the set to exceedspecification limits.The voltage adjust device alsomust be capable in some cases of providing an oper-ating voltage other than rated voltage for specialtypes of equipment and to compensate for externalline drop.b. Apparatus.Instrumentation for measuringload conditions, ambient temperature, and thegenerator field (or exciter field) voltage and currentshall be as described and illustrated in MIL-HDBK-705.c. PreparationforTest.(1) Preparationfortest.(a) Connect the load and field instrumenta-tion in, accordance with the applicable figure of MIL-HDBK-705, Method 205.1, Paragraph 205.1.10 forone voltage and frequency.(b) No further adjustments shall be made toany set control for the remainder of this test exceptthe control panel voltage adjust device.(c) Record all instrument readings.(d) Remove load.(e) Record all instrument readings (aftertransients-have subsided).(f) Adjust the terminal voltage to the maxi-mum specified value.(g) Record all instrument readings.NOTEAt voltages above rated values, thegenerator will be supplying less thanrated current; and at voltages belowrated values, the generator will besupplying greater than rated current.Caution should be taken to avoiddamage to instrumentation and loadbanks.(h) Apply rated load (rated kw at rated powerfactor).(i) Record all instrument readings (aftertransients–have subsided).(j) Remove load and adjust voltage to themaximum attainable value or to a value just prior toactuation of the overvoltage protection device.16-4
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business