available to the operator, specifically adjustmentsto the voltage or frequency adjust devices. On gen-erator sets utilizing a droop-type speed controlsystem as the prime speed control, the speed anddroop portions of the control may be adjusted. Noother adjustments to the voltage and frequency con-trol systems shall be made.Adjustments to theload, voltage or frequency controls shall be re-corded on both the data sheet and recording chart(s).Stabilization will be considered to have occurred whenfour consecutive voltage and current recordings ofthe exciter field either remain unchanged or have onlyminor variations about an equilibrium condition withno evident continued increase or decrease in valueafter the last adjustment to the load, voltage or fre-quency has been made.(b) Perform this test using resistive loadonly.Remove reactive load after stabilization.(c) For sets with droop-type governors:1. Load the set to 125% of rated load.Adjust the frequency to the rated value and maintainthe load for 5 minutes.(d) For generator sets with isochronous-type governors, repeat step (c) above but do not ad-just the frequency.(e) Results. Compare these results withthe requirement of Table 16-1.16-25. Under Frequency Protective Device Test.a. General.For generators that power certaintypes of equipment, it is extremely important thatthe circuit interrupter open when the frequency failsappreciably below rated value. Severe damage mayotherwise result to the powered equipment. To insurethat the circuit interrupter will open at or before thecritical frequency value, the generators are equip-ped with an underfrequency protective device. Thedevice on this generator operates electrically. Al-though the under frequency protective device must becapable of functioning at any voltage throughout thespecified voltage operating range, it is necessaryonly to perform the test at the specified maximum, atrated, and at minimum voltage limits.b. Apparatus.Instrumentation for measuring loadconditions shall be as described and illustrated inmethod 205.1, paragraph 205.1.10 of MIL-HDBK-705.c.Procedure.(1) PreparationForTest. Connect a voltmeterand frequency meter to the generator set terminals,ahead of the circuit interrupter, and the remainder ofthe apparatus as shown in the applicable figure ofparagraph 205.1.10 of MIL-HDBK-705.(2) Test.(a) Operate the generator at rated speed andvoltage, and at no load since the generator is equippedwith an electrical-type underfrequency protective de-vice, this test shall be repeated with the voltage ad-justed to maximum and minimum voltage for the speci-fied voltage operating range.(b) With the circuit interrupter closed, slowlydecrease the operating speed until the protective de-vice causes the circuit interrupter to open. The elec-tric governor must be deactivated to sufficiently de-crease the speed on Class 1, precise sets.(c) Record the speed.(d) Repeat the test while rapidly decreasingthe operating speed. Again record the speed.(e) Operate the generator at rated speed andvoltage, and at rated load.(f) Repeat steps (b), (c) and (d).d. Results. Compare the test value of frequencywith that given Table 16-1.16-14
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business