Figure 3-8. Lamp and fuse replacement.
Table 3-3. Troubleshooting

Generator Set, Diesel Engine: 200 Kw, 60 Cycle, Ac, 120/208V, 240/416V, 3 Phase. Convertible Fo 167 Kw, 50 Cycle 120/208V, 240/416V, 3 Phase Page Navigation
  34    35    36    37    38  39  40    41    42    43    44  
img
. . . .
TM 5-6115-400-12
Figure 3-9. Moisture collector manifold drain.
Section V. TROUBLESHOOTING
3-15. General
3-16. Troubleshooting Table
This section provides information useful in diagnosing
Malfunctions which may occur are listed in table 3-3.
unsatisfactory operation or failure of the generator set or
Each malfunction stated is followed by a list of probable
its components.
causes  of  the  trouble.
The  corrective  action
recommended is described opposite the probable cause.
Table 3-3. Troubleshooting
Malfunction
Probable cause
Corrective action
1.
Engine will not turn
a.
Batteries weak.
a.  Recharge or replace batteries
(para 3-62).
b.  Starter or starter solenoid
b.  Repair or replace starter or
switch inoperative.
starter solenoid switch (pare
3-56).
c.
Engine is locked or seized.
c.  Refer to higher echeon
2.
Engine hard to start
a.
Batteries weak.
a.  Recharge or replace batteries
(para 3-62).
b.
Incorrect grade of fuel.
b.  Drain fuel system. Fill the
tank with the specified fuel. Refer
to Appendix B.