Figure 3-3. Fuel Tank service.
Figure 3-6. Adjusting fan belts.

Generator Set, Diesel Engine: 200 Kw, 60 Cycle, Ac, 120/208V, 240/416V, 3 Phase. Convertible Fo 167 Kw, 50 Cycle 120/208V, 240/416V, 3 Phase Page Navigation
  30    31    32    33    34  35  36    37    38    39    40  
img
TM 5-6115-400-12
Figure 3-5 (2)-Continued.
Figure 3-5 (1). Fuel strainer and filter service.
3-14. Intake Manifold Moisture Collector
a. General.  A collector manifold (fig.  39) is
connected to each port of the intake manifold to collect
any condensation that may collect in the intake manifold
during shutdown periods.
b. Draining. Open the drain cock daily to drain any
accumulation of water in the collector manifold.
Note.  The drain cock must be closed when the
engine is operating.
Caution: If a considerable amount of coolant
has drained from the collector manifold, the
intercooler should be checked for leaks.
3-8