TM 9-6115-668-135.24 CONNECTOR RECEPTACLE L1 TO L3 AND N MAINTENANCE.This task covers:a. Removalb. InstallationINITIAL SETUPToolsEquipmentConditionsGeneral Mechanic’s Tool KitReference(item 2, appendix B)Generator Set 150 kW shut down,Automotive Fuel and Electrical System Repair, Tool Kitparagraph 2.5.2(item 3, appendix B)Socket wrench, shop manufactured(item 15, appendix B)Materials/PartsCable ties(item 10, appendix F)Loctite 243(item 16, appendix E)WARNINGDisconnect the negative battery cable first and then the positive bat-tery terminal cables. Failure to observe this warning could result inse-vere personal injury or death.C A U T I O NTag all cables prior to removal to ensure correct connection of the cablesduring installation.REMOVAL1.Remove unit hood assembly (1, figure 5-39) as instructed in paragraph 4.14.2.Open front panel (4) of control cabinet assembly (3) and secure with prop (5).3.Remove eighteen screws (6), eighteen serrated lock washers (7), and eighteen washers (8).4.Lower control cabinet connection panel (9) and prop with wooden boards.5.Remove connector receptacles L1 (16) and L3 (12):N O T ERemoval procedure for connector receptacle L3 (12) is the same as forconnector receptacle L1 (16), described below.a. Remove two nuts (47) from spacer (37) and remove clear plastic cover (46).b. Remove nut (39) from threaded terminal (38) while holding nut (44 or 45) with a suitable wrenchc. Remove serrated lock washer (40), washer (41), cable (42), and washer (43) from threaded ter-minal (38).5 - 1 5 8