TM 9-6115-668-134.84SCAVENGE PUMP ASSEMBLY MAINTENANCE.This task covers:a. Removalb. InstallationGeneral Mechanic’s Tool Kit(item 2, appendix B)Automotive Fuel and Electrical System Repair, Tool Kit(item 3, appendix B)ReferenceGenerator Set 150 kW shutdown,paragraph 2.5.2Sealing ringSealing tape(item 19, appendix E)1. Open flap (2, figure 6-65) on unit hood assembly.Place a container underneath scavenge pump.2.Remove collar nut (21) from threaded bushing (20) on scavenge pump (6).3.Undo VELCRO strap and remove oil outlet pipe assembly (21 to 29).After removal, plug oil line (17) and tie up.4.Remove collar nut (11) from shutoff valve (18) and remove oil line (17).5.Remove two nuts (9) with two serrated lock washers (8) and two washers (7).6.Pull out two screws (4) with two washers (5) and remove scavenge pump (6) with shutoff valve (18)from holder (10).7.Using a suitable hold damp scavenge pump (6), unscrew shutoff valve (18) and set aside for re-use.8.Unscrew threaded bushing (20) from scavenge pump (6) and remove together with sealing ring(19). Discard sealing ring (19).NOTEUse new sealing ring (19) and new thread sealing taps.1.Clamp scavenge pump (6), wrap sealing tape around pump-end threads of shutoff valve (18) andscrew in shutoff valve (18).4-210