4.70 J1/120 V 400 HZ DOUBLE CONNECTOR RECEPTACLE MAINTENANCE.
This task covers:
a. Removal
b. Installation
Equipment Conditions
General Mechanics Tool Kit
(item 2, appendix B)
Automotive Fuel and Electrical System Repair, Tool Kit
(item 3, appendix B)
Materials/Parts
Reference
Generator Set 150 kW shut down,
paragraph 2.5.2
Cable ties
(item 10, appendix E)
WARNING
Disconnect the negative battery cable first and then the positive battery
terminal cables. Failure to observe this warning could result in severe per-
sonal injury or death.
CAUTION
Tag all cables prlor to removal to ensure correct connection of the cables dur-
ing installation.
1.
2.
3.
Remove unit hood assembly (1, figure 4-58) as instructed in paragraph 4.14.
Open front panel (4) of control cabinet assembly (3) and secure with prop (5).
Remove eighteen screws (6), eighteen serrated lock washers (7), and eighteen washers (8) from
panel (9).
4.
Lower control cabinet connection panel (9) and prop.
5.
Remove two nuts (42) and cover (43) from spacer (41).
NOTE
Retain varistor R9 for re-use.
6.
Remove screws (30) and cables (27, 29) and varistor R9 (28) from terminals of J1/120 V 400 Hz
double receptacle (26).
7.
8.
9.
Remove screw (20), cover (19) and seal (21).
Remove two nuts (25), two serrated lock washers (24), and two washers (23) from panel (9).
Pull J1/120 V 400 Hz double receptacle (26), and two screws (22), out of front of control cabinet
connection panel (9).
4-173