ARMY TM 9-6115-464-12
AIR FORCE TO 35C2-3-445-1
NAVY NAVFAC P-8-624-12
5-8
UNIT MAINTENANCE OF FUEL BURNING WINTERIZATION KIT, HEATER CONTROL.
a. Heater Control Assembly.
(1)
(2)
(3)
(4)
Removal
(a) Removal screws (Figure 5-3) and washers.
(b) Pull control assembly out from generator set and disconnect electrical connectors.
Cleaning and Inspection.
(a)
(b)
(c)
Clean heater control assembly with filtered compressed air and an electricians brush or wipe
with a clean, lint-free cloth lightly moistened with an approved solvent.
Visually inspect heater control assembly for cracks, corrosion, bent or broken connector pins and
other damage.
Replace control assembly if damage is noted.
Lamp Replacement.
(a) Unscrew lens (Figure 5-3).
(b) Depress lamp and rotate counterclockwise to remove from indicator light base.
(c) Insert replacement lamp into base. Depress and rotate clockwise to lock in position.
(d) Install lens.
Installation.
(a) Connect electrical connectors and push control assembly into generator set.
(b) Install washers (Figure 5-3) and screws.
Figure 5-3. Fuel Burning Winterization Kit Heater Control Assembly Maintenance
5-6