TM 5-6115-593-34
NAVFAC P-8-631-34
TO-35C2-3-463-2
17-67. A motor starter will cause the fuel oil transfer
pump to operate when its pilot circuit is closed by the
action of the float switch. Fuel is then drawn from the
auxiliary tank via a foot valve and is pumped into the set
tank. Operation continued until the fuel level in the set
tank causes the float to rise, opening the float switch
and disconnecting the fuel transfer pump motor from the
power supply.
17-68. FUEL LEVEL INDICATING SYSTEMS . When
remote indication of the quantity of fuel in an
underground tank is required, a levelometer system can
be provided. Two types are available. The automatic
type operated by compressed air can be located up to
1000 feet (300 m) from gauged. The manually operated
type makes use of a hand pump located in the indicator
case and can be located up to 150 feet (45 m) from the
tank. Dials for the levelometer gauges can be supplied
calibrated in pounds, gallons, liters, feet, inches or any
other unit of measurement.
17-69. A typical levelometer system is shown in figure
17-19. Levelometers should be used only with vented
tanks.
17-70. FUEL AND LUBRICANTS . The set is capable
of
satisfactorily
starting
and
operating
on
fuels
conforming to VV-F-800 Grades DF-A and DF-2, MIL-
F16884, and turbine fuel conforming to MIL-T-5624
Grade JP-5. All components of the engine and fuel
system are capable of operating on Grade JP-5 turbine
fuel, except that rated load may be reduced to a
maximum of 20 percent of rated kw. When operated
continuously on Grade JP-5 fuel, the set meets all
requirements except that the injectors and fuel pumps
may be changed and timing adjusted from the diesel
setting at the time of changing fuel. The set is capable
of continuous operation using lubricating oil conforming
to MIL-L-9000, MIL-L-46167, and MIL-L-2104.
Section VIII. EXHAUST SYSTEM
17-71. The engine exhaust system must dispose of the
exhaust gases remaining after combustion with a
minimum of back pressure applied to the engine. The
exhaust gas flow for any engine will be approximately
three times the engine's intake and consumption. The
adverse effects of materially exceeding back pressure
recommendations of the engine manufacturers loss of
power,
poor
fuel
economy,
high
combustion
temperatures resulting in shorter service life, jacket
water
overheating,
and
crankcase
sludging
and
corrosion or bearing damage. When the generator set is
installed indoors, the exhaust system back pressure can
be kept within the acceptable limits by the selection of
properly sized and installed exhaust pipe and the use of
the two mufflers supplied with the set.
17-72. When the generator set is installed indoors, it is
desirable but not mandatory, to have the mufflers
outdoors.
This
will
greatly
reduce
the
heat
radiated within the building; insulating the exhaust piping
with asbestos will further reduce radiated heat.
17-73. To ensure an exhaust system which will not
produce a back pressure in excess of the engine
manufacturer's specifications (shown in table 17-7).
a. Use an exhaust flex connector not less than 5
inch (12.7 cm) ID.
b. Use the silencers supplied with the generator
set.
c.
Do not exceed the maximum equivalent
exhaust pipe length in feet in table 17-8.
17-24