TM5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2Figure 12-2. Actuator Test Circuitshaft towards maximum fuel and counterclockwise tomove it towards minimum fuel.(8) Set test circuit to CENTER. Observe and notedirection and position of terminal shaftmovement.(a) If terminal shaft moves to anotherposition set test circuit to OFF.1.For a clockwisemovement turn pilot valve plungerscrew (63) slightlycounterclockwise.2.For a counterclockwisemovement turn screw (63) slightlycounterclockwise.3.Note the new position forreference in case more adjustmentis needed.4.Repeat steps 8(a)1. and 3. or8 (a) 2. and 3. until no movement of theterminal shaft occurs when the test circuit ismoved from OFF to ENTER. Continue onto step (9) and calibrate terminal shaft.(b) If terminal shaft did not movefrom its original position, the pilot valveplunger is centered. Continue to step (9)and calibrate terminal shaft.(9) Turn test circuit to OFF and set potentiometer to zeroma.CAUTIONDo not exceed 200 ma duringremainderoftesttopreventdamagetothemagneticpropertiesofthemagnet.(10) Set test circuit switch to NORMAL.(11) Adjust potentiometer to 20 ma.(12) Turn spring seat (56) counterclockwise until actuator terminal shaft12-3