TM 5-6115-593-12TO 35C2-3-463-1STEP 3.WHEN THE ENGINE HAS STARTED, ADJUST THE FREQUENCY AND VOLTAGE TO THE DESIREDVALUES.STEP 4.PRIOR TO CLOSING THE MAIN CIRCUIT BREAKER (AS EXPLAINED IN STEP 6, BELOW), CHECK GENFAULTINDICATORS BY PLACING ANNUNCIATORTESTSWITCH IN THE TEST POSITION. IF NONEOF TEE LIGHTS ARE ON AFTER BEING TESTED, PROCEED WITH STEP 5. IF A LIGHT DOES CONEON, CORRECT THE INDICATED FAULT BEFORE PROCEEDING.STEP 5.PLACE THE PARALLEL/SINGLEUNITOPERATION SWITCH IN THE SINGLEUNITOPERATIONPOSITION.STEP 6.PLACE THE ACPWRCKTBKRTO CLOSE POSITION FOR APPROXIMATELY 2 OR 3 SECONDS TOCLOSE THE MAIN CIRCUIT BREAKER. CLOSED INDICATOR SHOULD CONE ON.Figure 2-10. Starting Instructions when Ambient Temperature is from 40°F to-25°F (4.4°C to -32°C) and Housing Kit is Installed (Sheet 3 of 3)2-25