TM 5-6115-593-12
TO 35C2-3-463-1
STEP 3.
WHEN THE ENGINE HAS STARTED, ADJUST THE FREQUENCY AND VOLTAGE TO THE DESIRED
VALUES.
STEP 4.
PRIOR TO CLOSING THE MAIN CIRCUIT BREAKER (AS EXPLAINED IN STEP 6, BELOW), CHECK GEN
FAULT INDICATORS BY PLACING ANNUNCIATOR TEST SWITCH IN THE TEST POSITION. IF NONE
OF TEE LIGHTS ARE ON AFTER BEING TESTED, PROCEED WITH STEP 5. IF A LIGHT DOES CONE
ON, CORRECT THE INDICATED FAULT BEFORE PROCEEDING.
STEP 5.
PLACE THE PARALLEL/SINGLE UNIT OPERATION SWITCH IN THE SINGLE UNIT OPERATION
POSITION.
STEP 6.
PLACE THE AC PWR CKT BKR TO CLOSE POSITION FOR APPROXIMATELY 2 OR 3 SECONDS TO
CLOSE THE MAIN CIRCUIT BREAKER. CLOSED INDICATOR SHOULD CONE ON.
Figure 2-10. Starting Instructions when Ambient Temperature is from 40°F to
-25°F (4.4°C to -32°C) and Housing Kit is Installed (Sheet 3 of 3)
2-25