TM 5-6115-593-12
TO 35C2-3-463-1
Table 2-5. Remote Control Panel, Controls and Instruments-Continued
FIGURE,
NORMAL
INDEX NO.
CONTROL AND INSTRUMENT
FUNCTION
READING/SETTING
2-13,10
AMMETER meter
Indicates percent rated
Less than 100%
current for selected
phase.
2-13,11
KW meter
Indicates power output
Less than 100%
of 3-phase, 4-wire
generator
2-13,12
OVER CRANK lamp
Lights if cranking time
OFF
has been exceeded.
2-13,13
ENG FAULT indicators
Indicates engine fault.
OFF
HI COOL TEMP
Lights if coolant
OFF
temperature rises
above 213 3°F
(100 + 0.7xC).
HI LUB TEMP
Lights if lube tempera-
OFF
ture rises above 255
3°F (124 1°C).
LOW OIL PRESS
Lights if oil pressure
OFF
drops below 21 2 psi
(1.47 kg/cm2 ).
LOW FUEL LEVEL
Lights indicating fuel
OFF
in day tank at a low
level (1-hour opera-
tion).
OVERSPEED
Lights if engine speed
OFF
reaches 2200 to
2300 rpm.
2-13,14
ANNUNCIATOR RESET
Resets annunciating
OFF
switch
system.
2-13,15
ALARM SILENCE switch
Silences alarm
OFF
2-13,16
ANNUNCIATOR TEST
Activates audible
OFF
switch
alarm and checks
indicator bulbs.
2-13,17
GEN FAULT indicators
Indicates generator
OFF
fault
OVERLOAD
Lights if any phase cur-
OFF
rent exceeds 110 per-
cent rated load.
OVERVOLT
Indicates an overvoltage
OFF
condition.
UNDERVOLT
Indicates an undervolt-
OFF
age condition.
REVERSE POWER
Indicates a reverse
OFF
power condition.
2-30