Table 2-5. Remote Control Panel, Controls and Instruments-Continued
FIGURE,
NORMAL
INDEX NO.
CONTROL AND INSTRUMENT
FUNCTION
READING/SETTING
2-13,17
SHORT CIRCUIT
Indicates a short
OFF
(cont'd)
circuit.
2-13,18
KVAR meter
Indicates KVAR of 3-
Less than 100%
phase, 4-wire circuits.
2-13,19
Panel lamps
Four lamps to illuminate
panel.
2-13,20
SYNC lamps
Indicates synchronize-
OFF
tion of frequency for
paralleling of genera-
tor set.
2-13,21
POWER FACTOR meter
Indicates power factor of
0.8 lagging to
generator set load.
1.0
2-13,22
PARALLEL lamp
Lights indicating that
OFF
PARALLEL switch is on
parallel position.
2-13,23
PARALLEL OPERATION-
In PARALLEL OPERATION
As required.
SINGLE UNIT OPERATION
position activates all
parallel circuits; in
SINGLE UNIT OPERATION
position it deactivates
all parallel circuits.
2-13,24'
SYNCHROSCOPE meter
Indicates synchronization
Floats
of frequency of paral-
leling of generator set.
2-13,25
AC PWR CKT BKR-CLOSED
Indicates AC PWR CKT BKR
lamp
is in CLOSED position.
2-13,26
AC PWR CKT BKR-CLOSED-
Closes/opens AC power
Neutral
OPEN circuit breaker
circuit breaker.
switch
2-13,27
BATTLE SHORT ON-OFF
Bypasses generator set
OFF
switch
protective circuits
during an emergency
except over-speed and
short circuits.
2-13,28
READY-TO-LOAD
Indicates unit is ready
for loading.
2-13,29
EMERGENCY SHUT-DOWN-
Controls 24V DC to con-
ON-OFF switch
trol circuits to shut
down engine.
2-13,30
TELJACK
Allows telephone connec-
tion from generator set.
2-13,31
PANEL LT SW ON-OFF
Switches panel lamps on
switch
and off.
2-31