TM 5-6115-465-12
TO 35C2-3-446-1
NAVFAC P-8-625-12
TM 06858B/06859D-12
ALWAYS CHECK THE POSITION OF THE GENERATOR
SET VOLTAGE RECONNECTION BOARD BEFORE
PLACING THE LOAD BANK IN OPERATION. DAMAGE
TO THE LOAD BANK WILL RESULT IF IT IS OPERATED
AT A VOLTAGE DIFFERENT FROM THE GENERATOR
SET OUTPUT VOLTAGE.
STEP 1. CONNECT THE VOLTAGE SELECTOR WIRING HARNESS TO THE VOLTAGE SELECTOR
CONNECTOR CORRESPONDING TO THE GENERATOR SET OPERATING VOLTAGE.
STEP 2. INSTALL THE PROTECTIVE CAP OVER THE REMAINING CONNECTOR.
DO NOT ALLOW THE GENERATOR SET TO OPERATE
UNATTENDED WITH THE MODE SWITCH IN THE
MANUAL POSITION.
STEP 3. PLACE THE MODE SWITCH IN THE DESIRED OPERATING POSITION.
STEP 4. POSITION THE OVER TEMPERATURE RESET SWITCH TO THE ON POSITION.
CAUTION
DO NOT ALLOW LOAD BANK AND GENERATOR SET LOAD
TO EXCEED THE RATED LOAD OF THE GENERATOR SET.
STEP 5. POSITION THE LOAD SELECTOR SWITCH TO THE PERCENT LOAD WHICH, WHEN ADDED
TO THE GENERATOR SET LOAD, WILL MOST NEARLY EQUAL, BUT NOT EXCEED, 100
PERCENT OF THE GENERATOR SET RATED LOAD.
STEP 6. CHECK THAT LOAD BANK POWER ON INDICATOR LIGHT IS LIT. IF IT IS NOT, PRESS
IN ON THE LENS. IF THE LAMP ILLUMINATES BUT GOES OUT WHEN RELEASED, RE -
TURN THE LOAD SELECTOR SWITCH TO THE OFF POSITION. NOTIFY MAINTENANCE
PERSONNEL.
STEP 7. TO REMOVE THE LOAD BANK FROM OPERATION, POSITION THE LOAD SELECTOR
SWITCH TO THE OFF POSITION AND PLACE THE OVER TEMPERATURE RESET SWITCH
TO THE OFF POSITION.