TM 5-6115-465-12
TO 35C2-3-446-1
NAVFAC P-8-625-12
TM 06858B/06859D-12
DO NOT ATTEMPT TO OPERATE THE ELECTRIC
WINTERIZATION KIT IF THE GENERATOR SET IS
EQUIPPED WITH A FUEL BURNING WINTERIZATION
KIT WHICH IS OPERATING.
REFER TO THE ELECTRIC WTNTERIZATION SYSTEM DIAGRAM AND INSTRUCTIONS
NOTE:
PLATE LOCATED ON THE INSIDE FACE OF THE LEFT SIDE ENGINE COMPARTMENT
ACCESS DOOR FOR ADDITIONAL INFORMATION.
STEP 1.
IF THE GENERATOR SET IS EQUIPPED WITH A FUEL BURNING WINTERIZATION KIT,
TURN THE HANDLE OF THE THREE-WAY VALVE IN THE OIL PAN COOLANT LINE
UNTIL THE POINTER IS IN THE 12 O'CLOCK POSITION.
STEP 2.
OPEN BOTH SHUTOFF VALVES IN THE CYLINDER BLOCK COOLANT LINES.
DEPRESS THE CIRCUIT BREAKER TO ENERGIZE THE HEATER CONTROL CIRCUITS.
STEP 3.
STEP 4.
DEPRESS POWER ON AND HEATER ON INDICATOR LIGHTS. IF THEY DO NOT ILLUM-
INATE WHEN DEPRESSED, NOTIFY HIGHER LEVEL MAINTENANCE.
STEP 5.
PLACE ON-OFF SWITCH IN THE ON POSITION. IF BOTH POWER ON AND HEATER ON
INDICATOR LIGHTS DO NOT ILLUMINATE, CHECK FUSE. IF FUSE IS SERVICEABLE,
OPERATION AND NOTIFY HIGHER LEVEL MAINTENANCE.
PRIOR TO STARTING THE GENERATOR SET, TURN THE THREE-WAY VALVE HANDLE!
STEP 6.
UNTIL THE POINTER IS IN THE 9 O'CLOCK POSITION AND CLOSE BOTH SHUTOFF
VALVES IN THE CYLINDER BLOCK COOLANT LINES.
STEP 7.
PLACE THE ON-OFF SWITCH IN THE OFF POSITION.
DO NOT START THE GENERATOR SET WHILE THE ON-
OFF SWITCH IS IN THE ON POSITION.