Figure 2-6 (7)-Continued
Figure 2-7. Starting instructions.

Generator Set, Diesel Engine: 200 Kw, 60 Cycle, Ac, 120/208V, 240/416V, 3 Phase. Convertible Fo 167 Kw, 50 Cycle 120/208V, 240/416V, 3 Phase Page Navigation
  12    13    14    15    16  17  18    19    20    21    22  
img
. . . . . . . . . . .
TM 5-6115 400-12
Section IV. OPERATION OF GENERATOR SET
Note.
2-11. General
If an  emergency situation  requires continued
operation of the generator se the protection bypass
switch (fig.  2-6 (2)) can be used to override all
a. The instructions in this section are published for
safety devices except the overspeed and short
the  information  and  guidance  of  the  personnel
circuit. Lift over and push switch to ON position.
responsible for the operation of the generator set.
Push the switch to OFF position as soon as
possible after the emergency has passed.
b. The operator must know how to perform every
operation of which the generator set is capable. This
2-14. Operation Under Usual Conditions
section gives instructions on starting, stopping, single
and parallel operation of the generator set. Since nearly
every job presents a different problem the operator may
a. General. The generator set can be operated as
have to vary given procedures to fit the individual job.
a single unit or in parallel with other units of this model.
2-12. Starting
Warning:
Do not operate the generator set
unless the ground terminal has been
a. Preparation for Starting.
connected to a suitable ground.
(1) Open the control panel doors and louver doors
Electrical faults in the generator set,
(fig. 1-1).
load lines, or load equipment can
(2) Perform the preventive maintenance checks
cause injury or electrocution from
and services (para 3-6).
contact with an ungrounded system.
(3) Make the necessary load connections to the
generator set (para 2-5).
b. Single-Unit Operation.
b. Normal Starting. Refer to figure 2-7 and start
the unit.
(1) Determine the load voltage requirements and
position the  voltage change board for the
Caution:
required voltage (para 2-5).
Never
discharge  ether
into
hot
engine.
Caution:
Do not close the AC power circuit
c. Cold Weather Starting. For temperatures below
breaker until it has been determined
-25F, refer to the winterization equipment (para 2-22)
that the load is equal to or under the
and ether primer operating instructions (para 2-23).
rated capacity of the unit.
2-13. Stopping
(2) Attach the load cables (para 2-5).
a. Normal Stopping. Refer to figure 2-8 and stop
(3) Set the 50/60 cycle selector switch (fig. 2-6 (3))
the unit.
for the desired frequency.
b.
Stopping by Safety Devices.
The
(4) Start the engine (para 2-12).
generator set is equipped with safety devices that will
automatically stop the engine in case of high coolant
(5) Refer to figure 2-9 and operate the generator
temperature, low oil pressure, engine overspeed,
set as a single unit.
overvoltage, or no fuel. When one of these abnormal
c. Parallel Operation.
conditions occurs, an electrical circuit is broken by the
Note.
applicable safety device and this causes engine to shut
Generator sees to be operated in parallel
down.
A short circuit, overload, undervoltage, or
must have the same voltage and frequency
reverse power protective relay will automatically open
rating.  They must be connected for the
the AC power circuit breaker but will not stop the engine.
correct  phase  rotation.
The  voltage
regulation characteristics should be similar
and engines should have the same peed
regulation characteristics.
(1) Connect the governor parallel cable between
units by plugging the cable into the parallel
receptacles of both units.
2-11