TM 9-6115-668-135.12 RELAY K19 AND K20 WITH RELAY SOCKET AND CONTACT BUSHINGS MAINTENANCE.This task covers:a. Removalb. InstallationToolsEquipmentConditionsGeneral Mechanic’s Tool KitReference(item 2, appendix B)Generator Set 150 kW shutAutomotive Fuel and Electrical System Repair, Tool Kitdown,(item 3, appendix B)paragraph 2.5.2Removal Tool, small(item 10, appendix B)Installation Tool, small(item 11, appendix B)Materials/PartsCable ties(item 10, appendix E)WARNINGDisconnect the negative battery cable first and then the positive bat-tery terminal cables. Failure to observe this warning could result in se-vere personal injury or death.CAUTIONTag all cables prior to removal to ensure correct connection of the cablesduring installation.1.Open flap (2, figure 5-27) on unit hood assembly (1).2.Open front panel (4) on control cabinet assembly (3) and secure with prop (5).3.Remove digital isochronous load sharing module N4 (36) as instructed in paragraph 5.11.N O T ERemoval procedure for relay K20 is the same as for relay K19, de-scribed below.4. Remove relay K19 (7):a. Remove two screws (20), two serrated lock washers (19), and two washers (18) from twothreaded elements (17).5-115
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business