TM 9-6115-662-13&P
Item
No.
24
Table 2-2. Operator Preventive Maintenance Checks and Services
for AN/MJQ-40, PU-803, and PU-804 (continued)
Location
Not Fully Mission
Interval
Item to Check/Service
Procedure
Capable if:
Before
Exhaust discharge contains deadly gases. DO NOT operate generator set in
enclosed areas unless exhaust is properly vented outside. Severe personal injury
or death due to carbon monoxide poisoning could result.
Before
GENERATOR SET -
continued
EXHAUST SYSTEM
Check muffler for evidence of
leakage and exhaust system for
corrosion, damage or missing
parts.
Muffler or exhaust
system damaged or
leaking.
25
AIR CLEANER ASSEMBLY
Inspect air cleaner assembly (26)
Loose or damaged
and piping (27) for loose or
connections.
damaged connections.
Inspect restriction indicator (28)
for clogged element. If indicator
shows red, notify next higher level
of maintenance.
Clogged element is
indicated or piping
and connections are
loose.
2-20