Item
No.
13
14
Table 2-2.
TM 9-6115-662-13&P
Operator Preventive Maintenance Checks and Services
for AN/MJQ-40, PU-803, and PU-804 (continued)
Location
Not Fully Mission
Interval
Item to Check/Service
Procedure
Capable if:
Before
GENERATOR SET
ACCOUSTICAL MATERIALS Ensure that accoustical materials.
located in the grill areas, are
secure, not damaged or missing.
With any access door open, the noise level of this generator set could cause
hearing damage. Hearing protection must be worn when working near the
generator set while working.
The fuels used in this generator set are highly explosive. DO NOT smoke or use
open flame when performing maintenance. Flames and explosion can occur,
resulting in severe personal injury or death.
Before
ENGINE ASSEMBLY
Visually inspect the generator
set for fuel, oil, and coolant
leaks. Check for proper ground
connections.
Visually inspect the engine for
missing, loose, or damaged
parts and hardware, and for
unusual wear or deterioration.
l DEAD CRANK switch to
NORMAL.
Any fuel leaks. Any
Class III oil or
coolant leaks.
Any condition that
renders power
unit/power plant not
mission capable.
2-17