TM 9-6115-662-13&Pg. Refer to table 5-7 and check continuity for each power lead, W-1 through W-5 (10).Table 5-7. Input Power Leads.Wire Identification From ToW-1 K1-A1 Unit A Generator Set L1W-2 K1-B1 Unit A Generator Set L2W-3 K1-C1 Unit A Generator Set L3W-4 Switch Box Assembly L0 Unit A Generator Set L4W-5 BUS BAR Unit A Generator Set GNDh. Refer to table 5-8 and check continuity for each electrical lead, W-11 through W-16 (17).Table 5-8. Output Power Leads.4. Test contactor asWire IdentificationW-11W-12W-13W-14W-15W-16follows:FromIToK1-A2K1-B2K1-C2K2-A2K2-B2K2-C2Switch Box Assembly L1Switch Box Assembly L2Switch Box Assembly L3Switch Box Assembly L1Switch Box Assembly L2Switch Box Assembly L3a. Using a multimeter, test contactor K1 (16) as follows:(1) Refer to figure 5-12 and perform following continuity checks. If any multimeter indication is notcorrect, replace contactor (paragraph 5-12).Lead PlacementContactorTerminalsMultimeterIndication32 and 33 continuity21 and 22 open circuit11 and 12 open circuitA1 and A2 open circuitB1 and B2 open circuitC1 and C2 open circuitA1 and B1 open circuitB1 and C1 open circuitC1 and A1 open circuit(2) Connect power supply VAC line to terminal X of contactor.5-20