TM 9-6115-660-13&Pc.d.e.f.g.Thread the fuel pickup tube (7) into the head (6). If the external fuel source is a 55-galloncontainer, thread the extension pipe (8) onto the fuel pickup tube (7).Remove the auxiliary fuel hose (4) from its storage location. It is stored in a compartmentbelow the generator set control panel, behind the bottom-right access door.Thread one end of the auxiliary fuel hose (4) onto the fitting on the container adapter (3).Tighten the connection.Connect the free end of the auxiliary fuel hose (4) to the generator set external fuel supplyconnection (1). The connection is located beside the generator set fuel tank filler neck. Tightenthe connection.Insert the container adapter (3) into the external fuel source (2). Secure the container adapterby pressing down on the handle of the clamp (5).WARNINGNever attempt to start the generator set if it is not properly grounded.Failure to observe this warning could result in severe personal injury ordeath by electrocution.Field Manual2-3.3 GroundingofGeneratorSet.Ground the equipment in accordance with ArmyFM 20-31. Typical ground rod installations are shown in figure 2-7. If a ground rod is used, install andconnect it as follows:Figure 2-6. Ground Rod and Slide Hammer.2-30