TM 9-6115-660-13&P
i. Disassemble slide hammer as follows:
(1) Remove nut (6, figure 2-6) from end of rod (4) and retain.
(2) Remove hammer (5) from rod (4) and thread nut (6) on end of rod to prevent loss.
(3) Store hammer (5) and rod (4) with assembled parts in accessory box.
2-3.4 Connecting Load.
2-3.4.1 Power Plant. Load cables and instructions for connecting them are normally furnished with the
equipment that is to be supplied with electric power. The load may be connected to the switch box
(1, figure 2-8) by either of two arrangements. One way is to connect a load cable to the switch box output
connector (7). The other way is to connect load cables to the switch box load terminals (3). Before
connecting the load, determine voltage requirements of the system or equipment that is to receive electric
power.
WARNING
Make sure generator sets are shut down before connecting load cables.
Failure to observe this warning can cause severe personal injury or death.
2-3.4.1.1 Connection to Output Connector.
a. Remove cap (6, figure 2-8) from output connector (7).
b. Connect load cable to output connector (7).
WARNING
Make sure generator sets are shut down before connecting load cables.
Failure to observe this warning can cause severe personal injury or death.
2-3.4.1.2 Connection to Switch Box Load Terminals.
a. Release both clamping catches (4, figure 2-8) and raise load terminal cover (2).
b. Select required output terminals from table 2-3.
CAUTION
When using single phase connections, always attempt to balance loads
between terminals (do not connect all loads between one terminal and L0).
Failure to observe this caution can result in damage to generator set.
NOTE
In five wire configuration, ground lead will be connected to ground
terminal (8).
2-33