TM 9-6115-660-13&PTable 2-2. Operator Preventive Maintenance Checks and Services - continuedLocationItemIntervalProcedureNot Fully MissionNo.Item to Capable if:Check/Service42DuringCONTROLS ANDObserve the following indicators and ensureFrequency or ACINDICATORSthey are operating properlyvoltmeterinoperative.COOLANT TEMP. 170-200°F (77-930C)OIL PRESSURE. 25-60 psi (172-414 kPa)FREQUENCY60 Hz (AN/MJQ-37,PU-798, and PU-798A);400 Hz (AN/MJQ-38,PU-799, and PU-799A)VOLTAGE120-240 Vac43DuringGROUND RODInspect ground rod and cable for looseCable is missingCABLE ANDconnections, breaks, damage and corrosionor damaged.CONNECTIONS44AfterHOUSINGa. Check doors, panels, hinges, and clampingCannot securecatches for damaged, loose, or corrodeddoors.items.b Inspect air intake and exhaust grills fordebris.45AfterIDENTIFICATIONCheck to ensure identification plates arePLATESsecure.46AfterSKID BASEInspect skid base for cracks and corrosionSkid base iscracked or showssigns ofstructuraldamage.47AfterENGINECheck for loose, damaged, or missingASSEMBLYhardware.48AfterFUEL SYSTEMInspect fuel system for leaks, and damaged,Any fuel leaks,loose, or missing hardwareand damaged,loose, or missingparts.WARNINGThe fuels used in this generator set are highly explosive. Do not smoke or use open flame whenperforming maintenance Flames and explosion can occur resulting in severe injury or death.Change 2 2-25