ARMY TM 9-6115-604-12NAVY NAVFAC P 8 633-124-103. SYNCHROSCOPE METER M106 (5, Figure 2-2).SYNCHROSCOPE meter M106 indicates the phase angledifference between the bus and a generator to be paralleled.a.Test. SYNCHROSCOPE meter M106 can be checked while Installed by comparing operation with thesynchronizing lights.(1) Start the generator set and place in parallel operation mode. Parallel generator set will provide bus voltagefor phase comparison against output voltage of generator set being tested.(2) With incoming unit operating at a higher frequency than the bus, SYNCHRONIZING LIGHTS DS110 andDS111 should be glowing light and dark. SYNCHROSCOPE meter M106 pointer should rotate in theclockwise (FAST) direction and should pass through the 12 o'clock position when the SYNCHRONIZINGLIGHTS are dark (center of dark period).(3) Lower frequency of incoming set using FREQ ADJ rheostat R102. SYNCHROSCOPE pointer should rotatein the counterclockwise (SLOW) direction but still pass through the 12 o'clock position when theSYNCHRONIZING LIGHTS are dark.(4) When the load circuit breaker CB101 is closed, and the generator set is In parallel with the bus, theSYNCHROSCOPE needle should be in the 12 o'clock positionb.Remove. See Figure 4-66.(1) Open cabinet B door Tag and disconnect wiring to SYNCHROSCOPE meter M106 (4)(2) Remove screws and remove SYNCHROSCOPE meter M106 (4) from front of cabinet B door.c.Install.See Figure 4-66.(1) Install SYNCHROSCOPE meter M106 (4) and secure In cabinet B door with screws provided.(2) Connect wiring and discard tags. Close cabinet B door.4-104. GEN TEMP GAGE M105 (10, Figure 2-2).GEN TEMP gage M105 indicates the temperature of any one of sixdetectors imbedded in generator G1 windings.a.Test.(1) Tag and disconnect wires to terminals 1 and 2 on rear of GEN TEMP gage M105.(2) Connect a 120V AC power source across terminals 1 and 2 on rear of GEN TEMP gage M105.(3) Set TEMPERATURE INDICATOR switch S113 to CAL, and note movement of indicator in GEN TEMP gageM105 Indicator should rest within the green area on the dial face of GEN TEMP gage M105.(4) If indicator of GEN TEMP gage M105 does not rest within the green area of the dial face, adjust GEN TEMPgage M105 In accordance with step c, below.(5) Replace GEN TEMP gage M105 if adjustment is not possible, or If indicator shows no signs of movementwhen tested.b.Remove.See Figure 4-66.(1) Tag and disconnect wires from GEN TEMP gage M105 (8).(2) Remove attaching hardware and remove GEN TEMP gage M105 (8) from front of cabinet B door.c.Install. See Figure 4-66.(1) Install GEN TEMP gage M105 (8) and secure in cabinet B door using mounting hardware provided.(2) Connect wiring and discard tags. Close cabinet B door.(3) While set Is operating, set TEMPERATURE INDICATOR switch S113 (13, Figure 2-2) to CAL, and adjustscrew on GEN TEMP gage M105 until needle is on green mark.4-168
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business