ARMY TM 9-6115-604-12NAVY NAVFAC P 8 633-124-98.AC KILOVOLTS METER M101 (2, Figure 2-2).AC KILOVOLTS meter M101 indicates generator output voltageor bus voltage depending on the setting of GEN/BUS VOLTMETER switch S112.a.Remove. See Figure 4-66(1) Open cabinet B door Tag and disconnect wiring to AC KILOVOLTS meter M101 (2).(2) Remove screws and remove AC KILOVOLTS METER M101 (2) from front of cabinet B door.b.TestBe sure power supply is deenergized before connecting meter. Death byelectrocution may result.(1) Connect AC KILOVOLTS meter to power supply with variable voltage output. The meter movement requires262 5 Vac 50/60 Hz for full scale meter deflection.(2) Turn on power supply.(3) Compare reading on AC KILOVOLTS meter against known output of power supply If reading differentiatesmore than 2 percent, replace meter.(4) Turn off power supply.(5) Disconnect meter.c.Install. See Figure 4-66.(1) Install AC KILOVOLTS meter M101 (2) and secure with screws provided.(2) Connect wiring and discard tags Close cabinet B door.4-99.FREQUENCY METER M103 (3, Figure 2-2).FREQUENCY meter M103 indicates frequency output ofgenerator G1.a.AdjustWith generator set shut down, check that needle on frequency meter M103 indicates at zero-adjust pointmarked on face of meter If necessary, adjust the screw on the face of the meter to align the needle with themark.b.Test.(1) Tag and disconnect wires from terminals 1 and 2 of frequency transducer A103 (See Figure 3-29).(2) Ensure that wires from terminals + and - of frequency transducer A103 are connected securely.(3) Connect a 120 V ac power source known to have a steady frequency across terminals 1 and 2 of frequencytransducer A103, and monitor FREQUENCY meter M103, located on cabinet B upper front door.(4) FREQUENCY meter M103 should Indicate a steady Hz value.(5) Replace FREQUENCY meter M103 If the Hz value indicated vanes by more than + 2 percent.c.Remove.See Figure 4-66.(1) Open cabinet B door. Tag and disconnect wiring to FREQUENCY meter M103 (3)(2) Remove attaching screws and remove FREQUENCY meter M103 (3) from cabinet B door.d.Install.See Figure 4-66.(1) Install FREQUENCY meter M103 (3) and secure In cabinet B door.(2) Connect wiring and discard tags. Close cabinet B door.4-165
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business