ARMY TM 9-6115-604-12
NAVY NAVFAC P 8 633-12
Figure 4-63. Cabinet A Upper Front Door Assembly
4-92. ANNUNCIATOR ALARM SYSTEM. The generator set annunciator alarm system consists of fault Indicator lights,
relays, an audible alarm, a pushbutton TEST switch, and an alarm silencing switch. The annunciator alarm system
indicates faults associated with generator set operation. See figure 4-63 Refer to paragraph 4-19.
a.
Test.
(1) Press and hold ANNUNCIATOR TEST pushbutton S15 (5, Figure 2-3).
(a) Audible alarm LS1 should sound. If horn does not sound, check horn in accordance with paragraph
4135.
4-159