ARMY TM 9-6115-464-12AIR FORCE TO 35C2-3-445-1NAVY NAVFAC P-8-624-12Table 5-4. Unit Troubleshooting For Fuel Burning Winterization Kit - ContinuedMALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION4.5.6.7.SURGING HEATER COMBUSTION.Step 1.Step 2.Step 3.Restriction in fuel line.Locate and remove restriction in fuel line.Defective generator set fuel transfer pumps.Replace fuel transfer pumps (para 4-27).Defective igniter assembly.Inspect and test igniter assembly. Replace if necessary (para 5-8).HEATER COMBUSTION CONTINUES AFTER HEATER CONTROL SWITCH PLACED IN OFF POSITION.Flame switch out of adjustment.Adjust flame switch (para 5-8).HEATER DOES NOT COMPLETE PURGE CYCLE.Flame switch out of adjustment.Adjust flame switch (para 5-8).FAN CONTINUES TO OPERATE AFTER PURGE CYCLE.Step 1.Step 2.Flame switch out of adjustment.Adjust flame switch (para 5-8).Incorrect wiring connections.Check wiring for improper connections. Correct as necessary.5-17