Table 5-3. Operator Troubleshooting For Fuel Burning Winterization Kit
NOTE
Before you use this table, make sure you have performed your PMCS.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. PRESS-TO-TEST INDICATOR DOES NOT LIGHT WHEN PRESSED.
Circuit breaker open.
Reset circuit breaker (para 2-22).
2. HEATER CONTROL SWITCH PLACED IN ON POSITION BUT HEATER DOES NOT START.
Circuit breaker open.
Reset circuit breaker (para 2-22).
3. BLOWER OPERATES BUT HEATER DOES NOT IGNITE.
Step 1. Heater fuel shutoff valve closed.
Open fuel shutoff valve (para 2-22).
Step 2. Generator set fuel supply exhausted.
Service generator set fuel supply (para 3-45).
4. SURGING HEATER COMBUSTION.
Restriction in fuel line.
Locate and remove restriction in fuel line.
5. FAN CONTINUES TO OPERATE AFTER PURGE CYCLE.
Incorrect wiring connections.
Check wiring for improper connections. Correct as necessary.
5-15