ItemNo.1112131415ARMY TM 9-6115-464-12AIR FORCE TO 35C2-3-445-1NAVY NAVFAC P-8-624-12Table 4-1. Unit Preventive Maintenance Checks and Services - ContinuedIntervalWeeklyWeeklyMonthlyMonthlyMonthlyLocationItem toCheck\ServiceMain Fuel TankFuel PumpStrainersGenerator SetBatteriesV-BeltProcedureDrain water and sediment.NOTEIn freezing weather, drain shortly after op-eration. Allow to drain until fuel runs dear.Service (para 4-29, Figure 4-16).NOTEIn freezing weather, drain shortly afteroperation. Allow to drain until fuel runsdear.Check entire unit for missing, loose, or dam-aged parts and hardware, and for unusualwear or deterioration.Check electrolyte level. Check condition with ahydrometer. Add water as required (para 3-4).Inspect for worn, frayed, cracked, or oil-soakedbelt. Check adjustment. If adjustment is re-quired, adjust for a 1/2 inch deflection whenbelt is depressed at a point midway betweenalternator and water pump pulley (para 4-40).NotMissionCapable If:4-7
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business