5-58TM5-6115-634-14&PNAVFAC P-8-647-14&PT0-35C2-3-445-14TM-6115-14&P/15-29. TEST AND REPAIR REMOTE CONTROL UNIT (cont)g.Inspect all connections forcompliance with FO-2 wiringdiagram.Then remove tags.h.Replace wiring harness asfollows:(1)(2)(3)(4)(5)(6)(7)(8)(9)Tag and mark wires con-nected to switches, con-trols and indicators.Remove ring nut (3) fromJ29D connector (4). Removewiring harness.Get a new wiring harnessto tag and mark wires totag and mark wires toexact match with the oldwiring harness.Connect wires to controls,switches, and indicatorsper tags.Ensure all con-nections are in accordancewith the schematic diagram(FO-2).Solder connections to in-dicators in accordancewith MIL-STD-454.Secure wiring harness withwire straps.Install connector J29D (4)to with ring nut (3).Install control panel (2)to housing and secure withsix screws (1).Test the remote controlunit by operating thegenerator set in theremote mode.