TM5-6115-634-14&PNAVFAC P-8-647-14&PT0-35C2-3-445-14TM-6115-14&P/15-29.TEST AND REPAIR REMOTE CONTROL UNIT (cont)(3) Install rheostat (13) onpanel.Secure with nutand washer assembly (12).Then install knob (11).e.Replace ENG RUNNING, CONTACTORCLOSED and LOW FUEL lightassemblies as follows:(1) Tag wire leads connectedto terminals.(2) Use solder/desolder kit toremove solder from connec-tor terminals and discon-nect the wires.(3) Remove nut (14), lock-washer (15), and lightassembly (16) from panel.(4) Install light assembly(16) and secure it topanel with nut (14) andlockwasher (15).(5) Connect wires to terminalsand solder connections inaccordance with MIL-STD-454, requirement 5.f.Replace SYN LIGHT assembly asfollows:(1)(2)(3)(4)Tag and disconnect wireleads connected to terminals.Remove nut (17), toothwasher (18), flat washer(19), light assembly (20),and flat washer (21) frompanel.Get a replacement lightassembly (20) and installflat washers (21) and(19), tooth washer (18)and nut (17).Connect wires to terminals.5-57