TM5-6115-634-14&P
NAVFAC P-8-647-14&P
T0-35C2-3-445-14
TM-6115-14&P/1
MAINTENANCE REMOTE CONTROL UNIT
5-29.
TEST AND REPAIR REMOTE CONTROL UNIT
This task covers: a. Test
b. Repair
INITIAL SETUP
Tools
General Mechanics Tool Kit
5180-00-177-7033
Multimeter
6625-01-139-2512
Solder/Desolder Kit
3439-00-460-7198
Materials/Parts
Remote Control Unit
97403-13228E1869
TEST
1.
TEST INDICATOR LIGHT ASSEMBLIES.
a.
Remove LOW FUEL, ENG RUNNING
and CONTACTOR CLOSED lamps.
Use an ohmmeter to test the
lamps for burned out filaments.
Replace turned out lamps.
b.
Remove SYN LIGHT lamps. Use
an ohmmeter to test the lamps
for burned out filaments.
Replace burned out lamps.
2.
TEST SWITCHES, CONTROLS AND WIRING
HARNESS.
NOTE
Refer to FO-2 for the following
procedures.
a.
Connect ohmmeter leads across
J29D pins A and B. Toggle S18
to RUN position. Meter indi-
cation should be O ohms.
b.
Connect ohmmeter leads across
J29D, pins A and C.
Toggle
and hold S18 to START position.
Meter indication should be O ohms.
5-53