TM5-6115-634-14&P
NAVFAC P-8-647-14&P
T0-35C2-3-445-14
TM-6115-14&P/1
Equipment Conditions:
Reference
Para. 4-9 General Instructions.
MAINTENANCE OF CABLE PARALLELING
4-52. TEST PARALLELING CABLE
This task covers: a. Test
INITIAL SETUP
Tools
General Mechanics Tool Kit
5180-00-177-7033
Multimeter
6625-01-139-2512
Materials/Parts
Paralleling Cable
97403-13228E1947
TEST
TEST PARALLELING CABLE.
a. Use a multimeter and test for
pin-to-pin continuity (O ohms).
Test for open circuit (infinite
ohms) between each pin and pin-
to-connector at both ends of
the cable.
b.
If an open or short occurs
within the cable assembly,
replace the cable.
NOTE
FOLLOWON MAINTENANCE: Connect
Negative Battery Cable (Para.
4-10).
4-80