TM5-6115-634-14&PNAVFAC P-8-647-14&PT0-35C2-3-445-14TM-6115-14&P/1EquipmentConditions:ReferencePara. 4-9 General Instructions.MAINTENANCE OF CABLE PARALLELING4-52. TEST PARALLELING CABLEThis task covers: a. TestINITIAL SETUPToolsGeneral Mechanic’s Tool Kit5180-00-177-7033Multimeter6625-01-139-2512Materials/PartsParalleling Cable97403-13228E1947TESTTEST PARALLELING CABLE.a. Use a multimeter and test forpin-to-pin continuity (O ohms).Test for open circuit (infiniteohms) between each pin and pin-to-connector at both ends ofthe cable.b.If an open or short occurswithin the cable assembly,replace the cable.NOTEFOLLOWON MAINTENANCE: ConnectNegative Battery Cable (Para.4-10).4-80