TM5-6115-634-14&P
NAVFAC P-8-647-14&P
T0-35C2-3-445-14
TM-6115-14&P/1
for troubleshooting the generator set
FO-6 are troubleshooting schematic dia-
diesel engine and main generator assembly,
grams for use as necessary during trouble-
and TM9-2330-205-14&P for troubleshooting
shooting.
the trailer.
Fold outs FO-2 through
Table 5-1.
TROUBLESHOOTING
MALFUNCTION
TESTOR INSPECTION
CORRECTIVE ACTION
1.
REMOTE CONTROL UNIT INOPERATIVE
Refer to para. 5-29 and test remote control unit.
Replace faulty components.
2.
REMOTE FUNCTIONS BOX ASSEMBLY INOPERATIVE
Step 1.
Refer to para. 5-20 and test for continuity in wiring harness
from J29B to J29C.
If open circuits exist, replace the wiring harness.
Step 2.
Refer to para. 5-19, and test for continuity in the wiring
harness from J29A to J29 and JA.
If open circuits exist, replace the wiring harness.
Step 3.
Refer to para. 5-22, and test relays KA, KB, KC, KD and KE.
Replace faulty relay.
If relays are functional and fault still exists, replace
the remote functions box assembly.
3.
SPECIAL RELAY ASSEMBLY INOPERATIVE
Step 1.
Refer to para. 5-25 and test special relay assembly.
If faulty components are found, send to intermediate
general support maintenance.
Step 2.
Refer to figure 5-1, and test for continuity in wiring from
connector JA to TB102 and A5.
If an open circuit exists , repair wiring as necessary.
Step 3.
Refer to figure 5-1, and check for continuity in wiring between
connectors, terminal boards and switches.
If an open circuit exists, repair or replace the special
relay assembly.
5-2