TM5-6115-634-14&PNAVFAC P-8-647-14&PT0-35C2-3-445-14TM-6115-14&P/1MAINTENANCE OF CABLE ASSEMBLY POWER 25 FT.4-49. TEST AND REPLACE POWER CABLE, 25 FT.This task covers: a. Removalc. Installationb. TestINITIAL SETUPToolsGeneral Mechanic’s Tool Kit5180-00-177-7033Multimeter6625-01-139-2512Materials/PartsCable Assembly, Power, 25 ft.97403-13228E1944-2EquipmentConditions:ReferencePara. 4-9 General Instructions.REMOVALREMOVE 25 FT. POWER CABLE.Disconnect power cable connec-tors from the junction box onthe first power unit and fromthe connector plate on thesecond power unit. Refer toFigures 2-3 and 2-5.TESTTEST 25 FT. POWER CABLE.a.b.4-76Use a multimeter and test forpin-to-pin continuity (O ohms).Test for open circuit (infiniteohms) between each pin and pin-to-connector at both ends ofthe cable.If an open or short occurswithin the cable assembly,replace the cable.
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business