TM5-6115-634-14&PNAVFAC P-8-647-14&PT0-35C2-3-445-14TM-6115-14&P/1MAINTENANCE OF CONTROL CABLE, 100 FT.4-48. TEST AND REPLACE CONTROL CABLEThis task covers: a. Removalc. Installationb. TestINITIAL SETUPToolsGeneral Mechanic’s Tool Kit5180-00-177-7033Multimeter6625-01-139-2512Materials/PartsControl Cable, 100 ft.97403-13228E1946REMOVALREMOVE 100 FT. CONTROL CABLE.EquipmentConditions:ReferencePara. 4-9 General Instructions.Disconnect control cable con-nectors from the junction boxand remove the remote controlunit.Refer to Figures 2-3 and2-5.TESTTEST 100 FT. CONTROL CABLE.a.b.Use a multimeter and test forpin-to-pin continuity (O ohms).Test for open circuit (infiniteohms) between each pin and pin-to-connector at both ends ofthe cable.If an open or short occurswithin the cable assembly,replace the cable.4-74