TM 5-6115-593-12TO 35C2-3-463-1TABLE 3-2. OPERATOR/CREW PREVENTIVE MAINTENANCE CHECKS AND SERVICESNOTE:Within designated interval, these checks are to be performed in the order listed.B-BEFOREA-AFTERD-DURINGBDA1oBatteries andCheck batteries for elec-Cables are looserelated itemstrolyte level and check forElectrolyte level lowsecurity. Ref par. 2-13C.2oMuffler andInspect exhaust installationRain caps are stuckexhaustfor condition, security, andclosed.leakage. Check that raincaps move freely.3oGround TerminalCheck for proper groundUnit is not groundedconnection4ooControls andInspect for damage and looseinstrumentsmounting. Operate press-to-Engine Paneltest indicator. Check thefollowing for properoperation.Battery charging volts.Battery charging ammetergreen portion of scale.Fuel level gauge.Coolant temperature gauge180 to 200 F (81 to 93 C).Oil Pressure Gauge30 to255 psi (2.1 to 3.5kg/cm ).Generator PanelAC Voltmeter120/208, 240/416 volts*AC AmmeterNot to exceed 100%Kilowatt MeterNot to exceed 100%Frequency Meter50-60 Hz*4oFault IndictorsAll lamps out during opera-tion. Check lamp operationusing press to test switch.* These values are nominal, refer to paragraph 1-10 for permissible voltage or frequency operating range for unusual installations.INTERVALITEMNO.ITEM TO BEINSPECTEDEQUIPMENT ISNOT READY/AVAILABLE IF:PROCEDURESCHECK FOR AND HAVE REPAIREDOR ADJUSTED AS NECESSARY3-4