TM 5-6115-593-12TO 35C2-3-463-1Table 2-6. Automatic Control Module, Controls and InstrumentsFIGURE,NORMALINDEX NO.CONTROL AND INSTRUMENTFUNCTIONREADING/SETTING2-19,1UTILITY POWER AVAILABLEIndicates availabilityONLAMPof utility/bus voltagewithin proper limits.2-19,2MODE SELECTOR switchSelects whether loadT.D. Returnwill be transferredback to utility aftera predetermined timedelay, instantly, orwill not transfer atall until manuallyselected.2-19,3FREQUENCY SELECT switchSelects the proper tripAs requiredpoints of the overby systemand under frequencyrunningrelays.frequency.2-19,4A.C. UTILITY POWER FUSEProtects wiring of— —15Autility monitoringcircuit.2-19,5BR1-4 A.C. Fuses 5AProtects wiring of BR1— —thru BR4 circuitry.2-19,6Unit 1-4 D.C. Fuses 5AProtects D.C. 'sensing— —wires between units1 thru 4 and auto-matic control module.2-19,7MR1-4 A.C. Fuses 5AProtects wiring of MR1— —thru MR4 circuitry.2-19,8MASTER CONTROL RELAYCloses the generator— —(MR1-MR4)circuit breaker onlyon the first unit toreach acceptablevoltage and frequency.2-19,9LOAD RELAYS LRRelay contacts will— —1 thru 4 and LRTDcontrol customer load1 thru 4feeder breakers.LRTD time delay re-lays adjustable from0.2 to 20 seconds.2-19,10OVER/UNDER VOLTAGE RELAYSenses utility voltage— —(27/59)at 120 10%. Tripsat 108V AC (under) and132V AC (over) voltage.2-19,11TIME DELAY RELAYAllows generator(s) toAs desired.(SDT)continue to run (cooldown) after utilitypower has returned.(Adjustable 1-300sec.)2-41