TM 5-6115-593-12TO 35C2-3-463-1A. DROOP PARALLELINGSTEP 1. ENSURE THAT A SHORTING PLUG IS INSTALLED IN ONE REACTIVELOADCOMPENSATIONCONNECTOR OR ON EACH SET AND THAT ALL FREQUENCYDROOP-ISOCHRONOUS SWITCHESARE IN DROOP POSITION. DESIGNATE ONE SET AS MASTER AND SECOND SET AS ONCOMING.WARNINGUSE EXTREME CAUTION. LOAD TERMINALS OF GENERATOR SET CIRCUIT BREAKER (CB2)MAY STILL BE ENERGIZED WITH THE BUS VOLTAGE. SERIOUS INJURY OR DEATH COULDRESULT.STEP 2. INERCONNECT POWEROUTPUTTERMINALS (LO-LO, L1-L1, L2-L2, L3-L3) OF THE TWO SETS. [THESEINTERCONNECTS SHOULD BE MADE VIA 3-PHASE DISCONNECT SWITCH (STATION SWITCH GEAR)ON THE LOAD SIDE OF EACH GENERATOR SET CIRCUIT BREAKER (CB2)].WARNINGDEATH OR SERIOUS INJURY NAY RESULT IF PERSONNEL FAIL TO OBSERVE SAFETYPRECAUTIONS. DO NOT ATTEMPT TO MAKE ANY CONNECTIONS UNTIL GENERATOR SET ISCOMPLETELY SHOT DOWN AND MAINTENANCELOCKOUT SWITCH IS IN LOCKOUT POSITION.STEP 3.PREPARE AND START MASTER SET PER INSTRUCTIONS GIVEN IN FIGURES 2-5 AND 2-8.STEP 4.ONCE AC PWR CKT BKR IS CLOSED, PLACE THE PARALLELOPERATION-SINGLEUNITOPERATIONSWITCH IN THE PARALLELPOSITION.STEP 5.START ONCOMING SET PER FIGURES 2-5 AND 2-8.STEP 6.CHECK PHASE SEQUENCE OF ONCOMING SET USING PHASE SEQUENCE 1-2-3 AND 1-3-2 LAMPS.ENSURE THAT SETS ARE IN SEQUENCE BEFORE PROCEEDING.STEP 7.PLACE PARALLELOPERATION-SINGLEUNITOPERATION SWITCH ON ONCOMING SET TOPARALLELOPERATIONPOSITION.STEP 8.SYNC LIGHTS AND SYNCHROSCOPE ON ONCOMING SET SHOULD NOW INDICATE THEDIFFERENCES IN VOLTAGE AND FREQUENCY BETWEEN THE TWO SETS.STEP 9.ADJUST THE FREQUENCY OF ONCOMING SET UNTIL THE SYNCLIGHTS ARE BLINKING VERYSLOWLY AND/OR SYNCHROSCOPE INDICATES THAT THE SETS ARE IN PHASE. THE ONCOMINGSET FREQUENCY SHOULD BE SLIGHTLY HIGHER AS INDICATED BY THE SYNCHROSCOPE.STEP 10.ADJUST THE VOLTAGE OF THE ONCOMING; SET USING VOLTMETERSELECTOR SWITCH ANDVOLTMETERUNTIL THE VOLTAGES ARE IDENTICAL.STEP 11.CLOSE THE ACPWRCKT BKR ON THE ONCOMING SET THE SYNCHLIGHTS ARE DARK AND THESYNCHROSCOPE NEEDLE IS IN THE 12 O'CLOCK POSITION.STEP 12.TRIM THE VOLTAGE AND FREQUENCY TO BALANCE THE LOAD ON BOTH SETS AS INDICATED BYTHE KVAR AND KW METERS. IF LOAD SHIFTS BETWEEN UNITS TRIM REACTIVELOADCOMPENSATIONCONTROLANDLOADGAIN SETTING ON GOVERNOR CONTROLLER.STEP 13.IF INCOMING SET IS ALREADY HOOKED UP, REPEAT STEPS 5 THRU 12.B. ISOCHRONOUS PARALLELING.STEP 1. REMOVE SHORTING PLUGS FROM ALL SETS AND INTERCONNECT REACTIVE LOAD COMPENSATIONAND GOVERNOR PARALLELING CIRCUIT CABLES.STEP 2. ENSURE THAT FREQUENCYDROOP-ISOCHRONOUS SWITCH IS IN THE ISOCHRONOUS POSITION.STEP 3.PROCEED AS IN A., ABOVE, STEPS 2 THROUGH 12.Figure 2-21. Operating Instructions, Manually Operatedin Parallel (Sheet 2 of 3)2-44
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business