TM 5-6115-593-12TO 35C2-3-463-1the slide hammer rod (2) if necessary, andplace the slide hammer (7) on top of the slidehammer rod. Slide down until it rests on thestriker plate (1). Attach nut (4) to the top ofthe slide hammer rod. Tighten to the end ofthe threads.(c) While holding in a vertical position, lift theslide hammer (7). Slide it downward to drivethe ground rod section (6) into the ground.Continue driving the ground rod section (6)until approximately 4 inches (10 centimeters)remains above ground level.(d) Disconnect the slide hammer assembly (8)from the ground rod coupler (5).(e) Attach the ground rod section (6) to theground rod coupler (5). Attach anotherground rod coupler (5) to the top of a newground rod section (6). Connect the slidehammer assembly (8) to the new ground rodcoupler (5).(f) Repeat steps (c), (d) and (e) until at least 8feet (2.4 meters) of ground rod is buried.Disconnect nut (4), and remove the slidehammer (7) from the slide hammer assembly(8). Disconnect the top ground rod coupler(5).(g) Connect a clamp (9) to top of the ground rodand reconnect the ground rod coupler (5).Connect loose end of the ground wireassembly to the clamp. Tighten the clampscrew (10). Ensure that all ground wireconnections are tight.g. ConnectingRemoteControlModule. Theremote control module can be located up to1000 feet (300 m) from the generator set.Refer to FO-14 and FO-9 for interconnectinginformation. Allow at least 3 feet (91 cm) infront and behind module for access duringmaintenance. Refer to par. 2-10.h. ConnectingAutomaticControlModule. Referto FO-15 for interconnecting diagram. Referto par. 2-11.4-4. EQUIPMENT CONVERSION.a. To convert generator set output voltage from120/280V AC to 240/416V AC, refer to figure4-8 and proceed as follows:WARNINGWhen making any electrical connections,make sure that the MAINTENANCE LOCKOUTswitch is in the MAINTENANCE position.(1) Unscrew fasteners on reconnection box coverand lift cover to obtain access to the movablejumpers.(2) Remove attaching hardware and adjustjumper bars for low wye, 120/208V AC (A,figure 4-8) or high wye, 240/416V AC (B,figure 4-8) configuration.(3) Securely reinstall attaching hardware andclose reconnection box cover.b. To convert generator set from 50 to 60 Hz,move the FREQUENCY SELECTOR switch(4, figure 2-3) to the desired position. Also, ifusing the automatic control module switch thefrequency select switch to the correspondingposition.4-13
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business