TM 5-6115-593-12TO 35C2-3-463-1WARNINGDO NOT OPERATE ENGINE GENERATOR SET UNLESS A GROUND CABLE HAS BEEN TO THE GOUNDTERMINAL STUD AND THEN TO A SUITABLE GROUND. ELECTRICAL FAULTS IN THE GENERATORSET, LOAD LINES OR LOAD EQUIPMENT, CAN CAUSE INJURY OR ELECTROCUTION FROMCONTACT WITH AN UNGROUNDED SYSTEM.NOTE: FOLLOW SLIDE HAMMER PROCEDURE IN PARAGRAPH 4.3 f.STEP 1. INSERT GROOUND CABLE INTO SLOT IN GROURD TERMINAL STUD AND TIGHTEN NUT.STEP 2. CONNECT COUPLING TO GROUND ROD AND INSERT SLIDE HAMMER IN COUPLING.STEP 3. DRIVE GROUND ROD INTO GROUND UNTIL COUPPLING IS JUST ABOVE TH GROUND LEVEL.STEP 4. CONNECT ADDITIONAL GROUND RODS, AS REQUIRED, BY REMOVING SLIDE HAMMER FROMCOUPLING AND INSTALLING ANOTHER GROUND ROD IN COUPLING. MAKE SURE EACH NEWGROUND ROD IS BOTTOMED ON ROD PREVIOUSLY INSTALLED. CONNECT ANOTHERCOUPLING ON NEW GROUND ROD AND INSERT SLIDE HAMMER.STEP 5. AFTER GROUND RODS HAVE BEEN DRIVEN INTO THE GROUND REMOVE SLIDE HAMMER ANDTOP COPLING.STEP 6. CONNECT CLAMP AND GROUND CABLE TO TOP OF EPOSED GROUD ROD AND SECURE BYTIGHTENING SCREW.Figure 4-7. Grounding Procedures (Sheet 2 of 3)4-10