TM 5-6115-584-12
NAVFAC P-8-622-12
TO 35C2-3-456-1
TM-05682C-12
OPERATING INSTRUCTIONS
BEFORE STARTING SET
1.
INSURE MAIN CIRCUIT BREAKER IS OFF.
2.
REMOVE ASK DOOR LABELED OIL-FILL, DRAIN, FILTER.
FILL CRANKCASE (DO NOT
OVERFILL).
FILL FUEL TANK.
ENSURE THAT VENT ON UNDERSIDE OF FUEL FILLER
CAP IS OPEN BEFORE STARTING GENERATOR SET.
3.
WARNING - GROUND SET TO AVOID SHOCK HAZARD.
LIFT FLAP ON ASK REAR PANEL
ASSEMBLY TO CHECK THAT GENERATOR SET IS PROPERLY GROUNDED.
4.
SET BATTERIES ARE NEGATIVE GROUND.
5.
INSURE ALL DOORS ARE IN PLACE, CLOSED AND LATCHED FOR OPERATION.
STARTING SET
1.
MOVE MASTER SWITCH TO PRIME & RUN POSITION TO ALLOW FUEL TO PRIME SET.
2.
MOVE MASTER SWITCH TO PREHEAT POSITION AND HOLD FOR (1) MINUTE.
NOTE:
PREHEAT IS NOT REQUIRED WHEN ENGINE IS HOT.
3.
MOVE
MASTER SWITCH TO START
POSITION AND HOLD UNTIL ENGINE FIRES
CONTINUOUSLY.
IF ENGINE DOES NOT START WITHIN 15 SECONDS, REPEAT STEPS 1
AND 2.
4.
MASTER SWITCH WILL RETURN TO PRIME & RUN POSITION WHEN RELEASED. IF
RUNNING FROM AUXILIARY FUEL SOURCE, MOVE MASTER SWITCH TO PRIME & RUN AUX
FUEL POSITION.
5.
AFTER WARM UP, CHECK FREQUENCY AND VOLTAGE AND ADJUST IF NECESSARY.
LIFT
FLAP LABELED SPEED CONTROL FOR SET FREQUENCY ADJUSTMENT.
6.
MOVE AC CIRCUIT BREAKER TO ON POSITION.
STOPPING SET
1.
MOVE AC CIRCUIT BREAKER TO OFF POSITION.
2.
MOVE MASTER SWITCH TO OFF POSITION.
3.
FOR EMERGENCY STOP, PULL DC CONTROL CIRCUIT BREAKER.
SERVICE INSTRUCTIONS
AMBIENT
FUELS
LUBRICATING OIL
TEMPERATURE
CAPACITY:
5KW-7 GAL 1OKW-12.5 GAL CAPACITY (LESS FILTER)
5KW-3 QT
1OKW-5.5 QT
PRIMARY-DIESEL
EMERGENCY-JP4
-65° TO -25° F
VV-F-800
-54° TO -32° C
FOR JP4 OPERATION
GRADE DFA
SEE INSTRUCTION
MIL-L-10295
. MANUAL
-25 TO -10 F
-32° TO -23 C
VV-F-800
GRADE DF1
-10°
TO +30° F
MIL-L-2104
-23° TO -1° C
GRADE 10
+30°
TO +100° F
-1°
TO +38° C
VV-F-800
GRADE DF2
MIL-L-2104
+100° TO +107° F
GRADE 30
+38° TO
+42° C
Figure 5-1.
Instruction and Rating Plates (Sheet 1 of 4)
Change 7
5-3