TM 5-6115-584-12NAVFAC P-8-622-12TO 35C2-3-456-1TM-05682C-12OPERATING INSTRUCTIONSBEFORE STARTING SET1.INSURE MAIN CIRCUIT BREAKER IS OFF.2.REMOVE ASK DOOR LABELED “OIL-FILL, DRAIN, FILTER”.FILL CRANKCASE (DO NOTOVERFILL).FILL FUEL TANK.ENSURE THAT VENT ON UNDERSIDE OF FUEL FILLERCAP IS OPEN BEFORE STARTING GENERATOR SET.3.‘WARNING” - GROUND SET TO AVOID SHOCK HAZARD.LIFT FLAP ON ASK REAR PANELASSEMBLY TO CHECK THAT GENERATOR SET IS PROPERLY GROUNDED.4.SET BATTERIES ARE NEGATIVE GROUND.5.INSURE ALL DOORS ARE IN PLACE, CLOSED AND LATCHED FOR OPERATION.STARTING SET1.MOVE “MASTER SWITCH” TO “PRIME & RUN” POSITION TO ALLOW FUEL TO PRIME SET.2.MOVE “MASTER SWITCH” TO “PREHEAT” POSITION AND HOLD FOR (1) MINUTE.NOTE:PREHEAT IS NOT REQUIRED WHEN ENGINE IS HOT.3.MOVE“MASTER SWITCH” TO “START”POSITION AND HOLD UNTIL ENGINE FIRESCONTINUOUSLY.IF ENGINE DOES NOT START WITHIN 15 SECONDS, REPEAT STEPS 1AND 2.4.“MASTER SWITCH” WILL RETURN TO “PRIME & RUN” POSITION WHEN RELEASED. IFRUNNING FROM AUXILIARY FUEL SOURCE, MOVE ‘MASTER SWITCH” TO “PRIME & RUN AUXFUEL” POSITION.5.AFTER WARM UP, CHECK FREQUENCY AND VOLTAGE AND ADJUST IF NECESSARY.LIFTFLAP LABELED ‘SPEED CONTROL” FOR SET FREQUENCY ADJUSTMENT.6.MOVE “AC CIRCUIT BREAKER” TO “ON” POSITION.STOPPING SET1.MOVE “AC CIRCUIT BREAKER” TO “OFF” POSITION.2.MOVE “MASTER SWITCH” TO ‘OFF” POSITION.3.FOR EMERGENCY STOP, PULL “DC CONTROL CIRCUIT BREAKER”.SERVICE INSTRUCTIONSAMBIENTFUELSLUBRICATING OILTEMPERATURECAPACITY:5KW-7GAL 1OKW-12.5 GAL CAPACITY (LESS FILTER)5KW-3 QT1OKW-5.5 QTPRIMARY-DIESELEMERGENCY-JP4-65° TO -25° FVV-F-800-54° TO -32° CFOR JP4 OPERATIONGRADE DFASEE INSTRUCTIONMIL-L-10295. MANUAL-25” TO -10” F-32° TO -23” CVV-F-800GRADE DF1-10°TO +30° FMIL-L-2104-23° TO -1° CGRADE 10+30°TO +100° F-1°TO +38° CVV-F-800GRADE DF2MIL-L-2104+100° TO +107° FGRADE 30+38° TO+42° CFigure 5-1.Instruction and Rating Plates (Sheet 1 of 4)Change 7 5-3
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business