(d) Slowly decrease the voltage at terminals1 and 2. The relay must reset when the voltage is8 ± vo1t ac.(7) To test the current transformer, proceedas follows:(a) Connect an ohmmeter across terminals1 and 2, and across 3 and 4. In each case, theresistance must be 0.34 ohms ± 10 percent.(b) Apply 15 Vac to terminals 1 and 2 withsecondary open circuit. The existing current mustbe less than 0.24 ampere.(c) Apply 15 Vac to terminals 1 and 2 withsecondary-Open circuit.The voltage across term-inals 3 and 4 must be 15 volts ac ± 1 percent.(7a) Test the total resistance of rheostat(R28), (Mode II). Total resistance should be15,000 ohms ± 10%. Test resistance between wiperarm and either end of rheostat. Resistance shouldvary between 0 and 15,000 ohms.(7b) Test the total resistance of rheostat(R29). Total resistance should be 12 ohms. Testresistance between wiper arm and either end ofrheostat. Resistance should vary between 0 and12 ohms.(7c) To test resistor assembly (A6) (Mode II)refer to paragraph (4a) and proceed as instructed.(7d) Check resistance of resistor (R31). Re-sistance should be 10 ohms.Change 1 8-19