(7) Panel light test.
( a ) Connect the positive lead of a variable
voltage dc power supply, adjusted for 24 Vdc, to pin
small v of receptacle J1.
( g ) Turn on the power supply.
( h ) The CKT. BRKR. light illuminates.
( i ) Turn off the power supply and discon-
nect the test leads.
( b ) Connect the negative lead of the power
supply to pin small r of receptacle Jl
(10) Battle short light test.
( c ) Place the PANEL LIGHT switch to the
ON position and observe the illumination of three
panel lights.
( a ) Connect the positive lead of a variable
voltage dc power suppy adjusted for 24 Vdc, to pin
small v of receptacle J1.
( d ) Place the PANEL LIGHT switch to the
OFF position.
( b ) Connect the negative lead of the power
supply to pin small r of receptacle J1.
( e ) Turn off the power supply and disconnect
the test leads.
( c ) Turn on the power supply.
( d ) The BATTLE SHORT light does not
illuminate.
(8) Air cleaner condition light test.
( a ) Connect the positive lead of a variable
voltage depower supply, adjusted for 24 Vdc to pin
small c of receptacle J1.
( e ) Depress the BATTLE SHORT light, the
light illuminates.
( f ) Turn off the power supply and connect
the position lead to pin R of receptacle J1.
( b ) Connect the negative lead of the power
supply to pin small r of receptacle J1.
( g ) Place the BATTLE SHORT switch to
the ON position, the BATTLE SHORT light illum-
inates.
( c ) Turn on the power supply.
( d ) The AIR CLEANER CONDITION light
does not illuminate.
( h ) Place the BATTLE SHORT switch to
the OFF position.
( e ) Depress the AIR CLEANER CONDITION
light, the light illuminates.
( i ) Turn off the power supply and discon-
nect the test leads.
( f ) Turn off the power supply and connect
the position lead to pin small u of receptacle J1.
(11) Synchronizing lamp test
( g ) Turn on the power supply.
( a ) Connect one lead of a 120 Vac power
supply to pin J of receptacle J1.
( h ) The AIR CLEANER CONDITION light
illuminates.
( b ) Connect the remaining lead of the
power supply to pin G of receptacle J1.
( i ) Turn off the power supply and disconnect
the test leads.
( c ) Turn on the power supply.
(9) Circuit breaker light test.
( d ) Place the unit operation switch to the
PARALLEL position.
( a ) Connect the positive lead of a variable
voltage dc power supply, adjusted for 24 Vdc, to
pin small v of receptacle Jl.
( e ) One of two synchronizing lamps (DS4)
shall illuminate.
( b ) Connect the negative lead of the power
supply to Fin small r of receptacle Jl.
( f ) Place the unit operation switch to the
single unit position.
( c ) Turn on the power supply.
( g ) Turn off the power supply and discon-
nect the test leads.
( d ) The CKT. BRKR. light does not illum-
inate.
( h ) Repeat the procedure b (11) (a) through
(g) for the-second synchronizing lamp (DS5) utiliz-
ing pins K and H of receptacle J1.
(e) Depress the CKT. BRKR. light, the
light illuminates.
(12) DC ammeter test
(f) Turn off the power supply and connect
the position lead to pin small a of receptacle J1.
(a) Connect a Simpson 260 or equivalent
3-8