Table 2-2. Generator Set Troubleshooting (Cont)MalfunctionProbable causeCorrective action36.Electric governor nota.Defective electrica.Isolate (para 7-2).—controlling set.governor control–Adjust, repair or replace as(Class I only)unit .required (para 7-2 and 7-4).b.Low hydraulicb.Isolate (para 14-14 and correctpressure.trouble. (para 14-15 and 14-16).c.Defective hydraulicc.Isolate (para 13-2).actuator.Repair or replace actuatoras required (para 13-3 thru 13-5).37.Generator sets will nota.Governor is nota.For a Class 1 set, Precise,parallel and shareadjusted cor-refer to paragraph 7-2.real (kw) load.rectly.b.Fuel injectionb.For a Class 11 set, Utility,—pump is notrefer to paragraph 14-45.adjusted pro-perly.38.Generator sets wilI notExciter regulator systemRefer to paragraph 8-14 for correctparallel and share re-including the reactiveadjustment procedures.active load.load sharing potentio-meter (R29) is not cor-rectly adjusted.NOTEAdditional troubleshooting proceduresare contained in Tables 8-1 and 14-1.Change 52-19