Table 2-2. Generator Set Troubleshooting (Cont)
Malfunction
Probable cause
Corrective action
27.
Generator runs at 130
a.
Defective overload
a.
Replace K14 (para 8-6
percent or more
relay (K14).
and 8-7).
rated current for
longer than 10 minutes,
b.
Defective re-
b.
Replace resistor R23, R24 or
CB2 does not open and
sisters R23, R24
R25, if ohmmeter test indi-
overload indicator does
or R25.
cates defect (fig. 8-2 and 8-3).
not light.
c.
Defective current
c.
Replace defective current
transformer CT1,
transformer CT1, CT2 or
CT2 or CT3.
CT3 (para 6-7 thru 6-8).
28.
Generator runs at
Defective overvoltage
Replace overvoltage relay (para 8-6
overvoltage (130
relay K2.
and 8-7).
percent. Set does
not shut down and
overvoltage indi-
cator does not light.
29.
Generator runs
Defective undervoltage
Replace undervoltage relay K11
under voltage (85 percent
relay Kilo
(para 8-6 and 8-7).
of rated voltage or less).
CB2 does not open and
undervoltage indicator
does not light
(Class I only)
30.
Percent power meter
Reverse power relay
Measure dc voltage at K15 terminals
reads down scale with
(K15) defective.
3 and 4. It should be 24 volts
2 or more sets paral-
(positive on terminal 3). Check
leled.
for Vdc at pins 1 and 2. If 2 or
more Vdc are present with 1 positive
replace reverse power relay (para
8-6 and 8-7).
31.
Set starts but will not
a.
System fault as
a.
Correct indicated fault.
run unless protection
indicated by
bypass switch (S7)
fault indicator
is closed.
panel.
b.
If no lamp is il-
b.
Replace any defective lamps.
luminated, press
fault indicator
test switch to
ensure that all
lamps are working.
NOTE
If the corrective action in a and b above does not correct
the malfunction, proceed to determine if one of the fol-
lowing components are defective by placing jumpers
across their contacts as follows:
c.
Overvoltage
c.
Terminals 3 and 4 of K2.
relay K2.
d.
Low oil pressure
d.
Terminal 3 of K2 and 4 of AS.
switch OP and high
coolant temperature
switch WT.
Change 5
2-17