Table 3-1. OPERATOR/CREW PREVENTIVE MAINTENANCE CHECKS AND SERVICES
B - BEFORE OPERATION
D -DURING OPERATION
A - AFTER OPERATION
ITEM
NO.
3
4
5
6
INTERVAL
B
l
l
D
l
A
l
l
l
ITEM TO BE
INSPECTED
PROCEDURES
EQUIPMENT WILL
BE REPORTED NOT
READY (RED) IF
h. Fault indicator
panel
Fuel tank
Oil level
Fuel filters and
strainers
Day Tank
All lights out during operation. Check bulb opera-
tion using test or reset switch on panel.
Fill fuel tank at completion of operation.
para 2-16b, 2-17c, 2-19, and 2-22)
(Fig. 1-2;
Check engine oil and add as required as indicated by
oil level gage. (Fig. 3-2; para 3-4a, 3-4b, 3-4c,
(l-9))
Check for leaks. Drain water and sediment.
NOTE
In freezing weather, drain shortly
after operation. Allow to drain
until fuel runs clear.
Drain water and sediment.
NOTE
In freezing weather, drain shortly
after operation. Allow to drain
until fuel runs clear.
Fault light will not extin-
guish when switch is placed
to TEST RESET position,
then released.
Class III leakage is detected.
Change 18
3-8.1 /(3.8-2 blank)